VLF vs. DC Hipot Kuenzanisa Tafura

 Oct 29, 2026

 Siya meseji

 

Tafura iri pazasi inopfupikisa misiyano mina yakasarudzika pakati penzira mbiri idzi, ichiteverwa nemisiyano yebvunzo-parameter inoteera kubva kwavari.

DC hipot test

Parameter

Kuedzwa kweVLF (0.1 Hz)

DC Hipot Testing

Advantage

Kugovera Munda

AC-kufanana. Capacitive uye resistive grading zvose zvinoshanda; kuparadzirwa kwekushushikana kunoburitsa mamiriro ebasa pa 0.1 Hz.

Kuramba chaiko. Munda unotongwa nekuita, kwete kubvumidzwa, saka magadhi egiredhi uye majoyometrie akabatanidzwa anosimbiswa zvakasiyana kubva kushumiro.

VLF

Space Charge Ngozi

Low. Polarity inodzosera kumashure ega ega 5 s; jekiseni rejaji rinosanganazve, uye tambo yacho haina kwayakarerekera mushure mebvunzo.

High. Charge yakavharirwa pamavoids, tsvina, uye nzvimbo dzepakati; residual field superimposes pa AC pa-re-energy uye inogona kukonzera post-test kukundikana.

VLF

Kuonekwa kweMuti weMvura

Ehe. Kudzokororwa kudzokororwa kwemunda kunoputsa muti-usina simba insulation pane kana pazasi bvunzo level; tan delta tip-up inoverengera kudzikira.

Kwete. Miti yemvura inonyatso kuoneka pasi peDC; yakaderedzwa tambo inopasa bvunzo uye inokundikana mubasa.

VLF

Equipment Size

Compact. Kuchaja ikozvino 500 × kuderera pane pa50 Hz, saka 30-80 kV set inorema 30-90 kg uye inomhanya kubva pa230 V socket.

Compact set, asi hapana yekuongorora kugona uye hapana kureba mukana; inoda imwe nzira yekubuda uye yepasi mushure mekuedzwa.

VLF

Test Voltage / Nguva

2U₀ kusvika 3U₀, 15-60 min (IEEE 400.2); 3U₀ ye15 min (HD 620 / VDE 0276-620).

Nhoroondo 2U₀ kusvika 4U₀ ye5-15 min; ikozvino yabviswa kune yakawedzera tambo neIEEE 400.2.

VLF

Diagnostics Available

Tan delta, PD kuyerwa, uye kuvuza ikozvino yekutarisa pane imwechete yekubatanidza.

Leakage current chete; hapana PD kana dielectric-kurasikirwa ruzivo.

VLF

Tumira Inquiry