Operational impulse bvunzo uye mheni kuvhundutsa bvunzo nzira mbiri dzakajairika dzepamusoro voltage bvunzo nzira, dzinonyanya kushandiswa kuongorora mashandiro ekudzivirira kwemidziyo yemagetsi. Kunyangwe iwo ese achisanganisira kupfuudza overvoltages, kune misiyano yakakura mune waveform, chinangwa uye mamiriro ekushandisa. Heino misiyano mikuru;
1. Mafungu akasiyana
Operational impulse test:
Waveform: 250/2500μs (wavefront nguva 250μs, hafu yepamusoro nguva 2500μs).
Zvimiro: Iyo waveform yenguva yakareba, simba rakakura, uye simulation operation overvoltage.
Mheni impulse test:
Waveform: 1.2/50μs (wavefront nguva 1.2μs, hafu yepamusoro nguva 50μs).
Zvimiro: Nguva yeWaveform ipfupi, yakakwirisa, uye nepamusoro pepamusoro, inoteedzera mheni overvoltage.
2. Zvinangwa zvekuedza zvakasiyana
Operational impulse test:
Tevedzera kushanda kwakawandisa mumagetsi sisitimu, senge switching mashandiro, kukanganisa kucheka uye mamwe maitiro enguva pfupi.
Ongorora maitiro ekudzivirira kwemidziyo pasi pekushanda overvoltage mamiriro.
Mheni impulse test:
Inotevedzera kupfuudza overvoltage inogadzirwa kana mheni ichirova midziyo kana mitsetse.
Ongorora maitiro ekudzivirira kwemidziyo pasi pemheni overvoltage mamiriro.
3. Mamiriro ekushandisa akasiyana
Operational impulse test:
Inonyanya kushandiswa mumagetsi system transformers, circuit breakers, tambo, uye zvimwe midziyo.
Inonyanya kukodzera kuongorora kuvimbika kwemidziyo pasi pekushanda overvoltage mamiriro.
Mheni impulse test:
Inoshanda kune ese midziyo yemagetsi inogona kurohwa nemheni, senge tambo dzekutumira, substation midziyo, nezvimwe.
Chengetedza zvakanyanya kusimba rekudzivirira kwemidziyo pasi penzvimbo yemheni.
4. The test voltage yakasiyana
Operational impulse test:
Iwo magetsi ekuyedza anowanzo 2-3 nguva yakayerwa voltage yemidziyo, uye kukosha chaiko kunotarwa zvichienderana nerudzi rwemidziyo uye zviyero.
Mheni impulse test:
Iyo bvunzo voltage yakakwira, kazhinji kakati wandei yakayerwa voltage yemidziyo, uye kukosha chaiko kunotemerwa zvinoenderana negiredhi rekudzivirira mheni uye chiyero.
5. Miyero yekuedza yakasiyana
Operational impulse test:
Teerera zviyero zvakaita seIEC 60060-1, GB/T 16927.1, nezvimwe.
Tarisa pakuenzanisa uye kuongororwa kwekushanda overvoltages.
Mheni impulse test:
Teerera nezviyero zvakaita seIEC 60060-1, GB/T 16927.1, IEEE C62.41, nezvimwe.
Iyo simulation uye kuongororwa kwemheni overvoltage inosimbiswa.