Substation Equipment Testing & Commissioning: Technical FAQ

 Oct 14, 2026

 Siya meseji

 

FAQ 1: Ndeupi musiyano uripo pakati pe "Pre-commissioning Tests" ne "Service Tests" muchiteshi?

Mhinduro:

Pre-commissioning Tests:Aya ndiwo "Deep Physicals" anoitwa mushure mekuiswa asi isati yasimba (kuchaja). Chinangwa ndechekuona kuti zvekufambisa uye kusangana kwemumunda hazvina kukanganisa asset. Miedzo yakakosha inosanganisiraTan Delta, Inoshandura Ratio,uyeAC Hipot.

Service (Maintenance) Miedzo:Inoitiswa nguva nenguva mushure mekunge midziyo yave kushanda. Izvi zvinotarisa paCondition-Based Maintenance (CBM)-kushandisa data sengeDGA (Dissolved Gas Analysis)uyeKuregererwa kwasara (PD)kufanotaura kukundikana zvisati zvaitika.

 

FAQ 2: Sei nzira ye "Zero-Compromise" yekuongororwa kweUnit Protection Stability yakakosha kumidziyo yeEHV?

Mhinduro:ZveExtra-High Voltage (EHV) zvinhu zvakaita se220kV kana 500kV transformers, kudzivirira ndiyo yekupedzisira yekuchengetedza mambure. Tinoita zvakasimbaYepuraimari uye Sekondari Jekiseni miedzokuve nechokwadi zveseYakarambidzwa Earth Fault (REF)uyeDifferential Protectionratidza kugadzikana kwakakwana kwe "out-of-zone" kukanganisa. Izvi zvinodzivirira kugumburwa, izvo zvinogona kukonzera kusagadzikana kukuru kwegridi uye kurasikirwa kwemari panguva yekunze kwehurongwa.

Do you know the Ratio Error & Accuracy Classes of CT - 0.2, 0.5, 5P20

FAQ 3: Ko zvemazuva ano CT/PT Analyzers inovandudza sei kushanda kwe substation commissioning?

Mhinduro:Kutumwa kwechinyakare kwaida midziyo inorema (150kg+) uye maawa ekugadzirisazve manyore paCT/PT yega yega. A yemazuva anoCT/PT Analyzerinoderedza giya kusvika 10kg sutukesi. Kushandisa theVariable Frequency Method, inogona kuyedza manyawi, chiyero, polarity, uye mhepo kuramba mune imwechete, otomatiki maminetsi maviri anoteedzana. Iyi "One-Connection" mafambiro ebasa anoderedza kutumwa nguva kusvika70%uye inobvisa kukanganisa kunyorwa kwevanhu.

 

FAQ 4: Sei kutariswa kwePatial Discharge (PD) kuchifanira kuitwa panguva yekuedzwa kweAC Hipot (Withstand)?

Mhinduro:Iyo AC Hipot bvunzo ndeye bhinary "Pass/Fail" cheki. Nekudaro, chikamu chinogona kupasa bvunzo yevoltage paine "ratent tumor" -a microscopic void kana burr iri kupenya. NekuitaUHF kana Acoustic PD yekutarisapanguva imwe chete, tinowana maonero ekuongorora. Kana PD mazinga akakwira pa80% bvunzo voltage, tinogona kumisa bvunzo uye kuferefeta, kudzivirira njodzi uye inodhura kuparara kweasset.

 

FAQ 5: Ndeapi maprotocol anosungirwa kuchengetedza usati wachaja shanduko yemagetsi panzvimbo ye220kV yechizvarwa?

Mhinduro:Pamusoro pekupfuura kwehunyanzvi, "Safe-to-Charge" chimiro chinoda:

Kuzviparadzanisa Nenyama:Kuve nechokwadi chekuti bvunzo dzese dzinotungamira dzabviswa uye zvisingaperi zvinongedzo zvinoiswa torque kune spec.

Kutsigira Kusimbisa:Comprehensive miedzo yeBuchholz relay, PRD (Pressure Relief Device), uye WTI/OTIrwendo interlocks.

Insulation Baseline:YokupedzisiraIR (Isulation Resistance)uyePI (Polarization Index)cheki yakanyorwa pakarepo pamberi simba simba kushanda sezvo mudziyo wacho "Birth Record."